A Solved problem to draw the per unit Reactance Diagram
Draw the per unit reactance diagram for the power systems shown below. Neglect resistance and use a base of 100MVA, 220KV in 50 ohms line. The ratings of the generator, motor and transformers are G: 40 MVA, 25 KV, X'' = 20%; M: 50 MVA, 11 KV, X'' = 30% T1:40 MVA, 33 Y / 220 Y KV, X = 15%; T2: 30 MVA, 11 Δ /220Y KV, X = 15% Load: 11 KV, 50MW + j68 MVAR Solution: Base MVAb new = 100 MVA; Base KVb new = 220 KV Transmission line j50 Ω: Zactual = j50 Ω Transformer T1: KVb old = 220 KV Generator G1: Transformer T2: KVb old = 220 KV (HT side voltage) Synchronous motor: Reactance diagram: |